The KL1512 Bus Terminal is a 2-channel up or down counter and transports the counter value electrically isolated to the higher-level automation device.
The KL2012 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation.
The KL2022 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. It handles different load currents, and its outputs are protected against short-circuit. The Bus Terminal contains two channels that indicate their signal state by means of light emitting diodes.
The KL2124 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation.
The KL2212 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation.
The KL2502 output terminal modulates the pulse width of a binary 24 V DC signal and outputs it electrically isolated from the K-bus. The mark/space ratio is prescribed by a 16 bit value from the automation device.
The KL3001 analog input terminal handles signals in the range from -10 to +10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device.
The KL3002 analog input terminal handles signals in the range from -10 to +10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device.
The KL3012 analog input terminal handles signals in the range from 0 to 20 mA. The current is digitized to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device.
The KL3021 analog input terminal handles signals in the range from 4 to 20 mA. The current is digitized to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device.
The KL3022 analog input terminal handles signals in the range from 4 to 20 mA. The current is digitized to a resolution of 12 bits and is transmitted, in an electrically isolated form, to the higher-level automation device.