The KL6021 serial interface allows devices with an RS422 or RS485 interface to be connected. The device connected to the terminal communicates with the automation device via the Bus Coupler.
The device connected to the terminal communicates with the automation device via the Bus Coupler. The active communication channel operates independently of the higher-level bus system in full duplex mode at up to 115.2 kbaud. The RS232 interface guarantees high immunity to interference through electrically isolated signals.
The KL6041 serial interface allows devices with an RS422 or RS485 interface to be connected. The device connected to the terminal communicates with the automation device via the Bus Coupler.
The KL6051 serial interface terminal makes it possible to exchange data between different fieldbus systems. Full duplex data exchange is possible, independently of the higher-level fieldbus. Under the terminal’s default setting, 32 inputs and 32 outputs are transferred between the fieldbus systems.
The KL6301 KNX/EIB Bus Terminal is integrated in an KNX/EIB network and can receive/transmit data from/to other KNX/EIB devices. Due to the integration in the Bus Terminal system, KNX/EIB components can also be integrated in higher-level bus systems such as Ethernet.
The KL6401 LON Bus Terminal enables direct connection of LON devices. The network variables of the connected devices are available for the Bus Coupler or the higher-level bus system.
The KL9010 bus end terminal is necessary for data exchange between the Bus Coupler and the Bus Terminals. Each assembly must be terminated at the right hand end with a KL9010 bus end terminal. The bus end terminal does not have any other function or connection facility.