The EL6021 serial interface enables the connection of devices with RS422 or RS485 interface. These devices communicate with the automation device via the coupler.
The EL6021-0021 serial interface enables the connection of devices with RS422 or RS485 interface. These devices communicate with the automation device via the coupler.
The EL6022 serial interface enables the connection of devices with two RS422/RS485 interfaces. The devices connected to the EL6022 EtherCAT Terminal communicate with the automation device via the Coupler.
The EL6631-0010 PROFINET RT device (slave) terminal enables simple exchange of data between EtherCAT and PROFINET RT. It is a device in the EtherCAT strand, which can consist of up to 65,535 devices.
Cycle times from 200 µs are possible. PROFIBUS DP, PROFIBUS DP-V1, PROFIBUS DP-V2 master and slave up to 12 Mbit/s powerful parameter and diagnostics interfaces The error management for each bus user is freely configurable. It is possible to read the bus configuration and automatically assign the “GSD” files.
The Interbus slave terminal facilitates data exchange between EtherCAT and Interbus. For both bus systems the terminal “mirrors” up to 32 word input and 32 word output to the respective other system.
The EL9210 potential feed terminal with fuse and diagnostics enables the setup of different potential groups with a fused standard voltage of 24 V DC. The supply voltage is taken up via the front terminal contacts, fused and passed through to the adjacent terminals via the internal power contacts. The fuse is a 6.3 A fuse, which can be replaced at the front.
The EL9505 power supply terminal takes the input voltage (24 V DC) and uses it to generate an output voltage of 5 V DC at 0.5 A, which can be tapped at the terminal.
The EL9510 power supply terminal takes the input voltage (24 V DC) and uses it to generate an output voltage of 10 V DC at 0.5 A, which can be tapped at the terminal.
The EL9512 power supply unit terminal generates an output voltage of 12 V DC from the 24 V DC input voltage. The output voltage can be accessed at the terminal.
The BC3100 Bus Terminal Controller is a Bus Coupler with integrated PLC functionality and has a fieldbus interface for PROFIBUS. It is an intelligent slave and can be used as distributed intelligence in the PROFIBUS system. In the BC3100, one unit consists of the controller, between 1 and 64 terminals, and a bus end terminal.